banner
Case

LM-4 Series

LM-4 Series Secondary Refrigerant Technical Guide
LM-4 general-purpose, LM-4D low-conductivity, LM-4D-YE ultra-low conductivity, LM-430 economical, LM-445 low-temperature, LM-495 high-alkalinity - complete technical guide for 6 LM-4 series products.

6 Product Models
Water-based Coolant
-20 to 150C

LM-4 Series Secondary Refrigerant Technical Guide

LM-4 general-purpose, LM-4D low-conductivity, LM-4D-YE ultra-low conductivity, LM-430 economical, LM-445 low-temperature, LM-495 high-alkalinity - complete technical guide for 6 LM-4 series products.

6 Product ModelsWater-based Coolant-20 to 150C

The Preferred General-Purpose Water-Based Coolant

The LM-4 series is the most widely applied general-purpose water-based coolant family in the Glacier Coolant product line. With excellent corrosion protection, high cost-effectiveness, and a wide temperature range (-20 to 150C), the LM-4 series has become the preferred solution for cold storage, HVAC, industrial refrigeration, and glycol/brine system replacement.

As a water-based coolant, the LM-4 series contains no organic solvents, is non-flammable and non-explosive, and is safe and environmentally friendly. Its proprietary corrosion inhibitor formulation effectively protects carbon steel, stainless steel, and other common materials, making it ideal for both new and converted systems.

LM-4Series Model Comparison

ModelTemperatureKey FeaturesTypical ApplicationsNotes
LM-4-20 to 150CGeneral-purpose, excellent corrosion protection, cost-effectiveCold storage, HVAC, industrial refrigeration, glycol replacementMild copper corrosion at high temps; monitor pH and inhibitor
LM-4D-20 to 150CLow conductivity, nitrite-free, copper-friendlyUltrasonic equipment, power electronics coolingMatch conductivity to customer requirements
LM-4D-YE-20 to 80CUltra-low conductivity (less than 800 uS/cm)Mixed-material systems (carbon steel + SS + copper + aluminum)Confirm specific conductivity requirements
LM-430-15C freezing pointEconomical antifreezeClosed cooling towers, standard freeze protectionSelect freezing point with safety margin; drain water before filling
LM-445-Low-temperature coolantMedium to low temperature industrial refrigerationFor cooling issues, check chiller area and pump flow first
LM-495-High reserve alkalinity typeSystems with special alkalinity requirementsReserve alkalinity > 12mL, pH 7.5-9.5, density 1.10-1.15, customizable

LM-4Series Key Advantages

Excellent Corrosion Protection

Proprietary inhibitor formulation effectively protects carbon steel and stainless steel. Long-term use requires periodic pH and inhibitor concentration monitoring.

High Cost-Effectiveness

As a general-purpose product, LM-4 offers outstanding cost advantages while meeting the vast majority of refrigeration needs.

Wide Temperature Range

-20 to 150C coverage, from frozen cold storage to high-temperature industrial refrigeration.

Easy System Replacement

Can directly replace glycol, brine, and propylene glycol systems with low conversion threshold.

Safe & Environmentally Friendly

Water-based formula, non-flammable and non-explosive, no special fire protection measures needed.

Low Conductivity Options

LM-4D and LM-4D-YE meet low conductivity requirements for power electronic equipment. LM-4D-YE is compatible with mixed-material systems.

LM-4Series Real Cases

2025.03.12LM-4
Sanchuan Chemical · Hebei Xingtai
Ammonia entered brine system; need to resolve corrosion
pH can be lowered with organic acids but cannot resolve root cause. Provided 2024 ammonia contamination sample results as reference
2025.04.22LM-4
Xinhua Insurance Data Center · Beijing
LM-4 turns black and foams
Sampled for testing
2025.04.26LM-4
Xinjiang Cold Storage · Xinjiang
LM-4 turns black, copper corrosion. Original system was ammonia storage conversion with refrigeration oil and ammonia residue
Recommended sampling to test if adjustable. Cold storage marginally profitable; replacement cost may be high
2025.04.28LM-4
Shandong Huatai · Shandong
LM-4 HCl contamination corrosion
Recommended adding enhancer and alkali for pH adjustment; monitor pH during operation; consider replacement
2025.05.26LM-4
Fujian Cold Storage · Fujian
Aluminum coil corrosion leaks; LM-4 used 2-3 years with multiple perforations
Sampling test shows no aluminum corrosion; cut pipe found crystalline substance. Planned analysis at Dalian University of Technology
2025.05.27LM-4
Huaqing Ronghao · Beijing
After adding 12.42t coolant, freezing point is -6°C; wants to adjust to -10°C
Calculated addition amount ~7t; recommended purchasing extra to prevent shortage
2025.06.18LM-4
Wanwei Group · Anhui Chaohu
Glycol system severe corrosion; PV polymer material contamination
Need sampling to test enhancer effectiveness. New system recommends LM-4; enhancer addition plan has risks
2025.06.19LM-4
Jinsheng Grain & Oil · Linyi
Cooling difficulties after adding enhancer; foam in tank
Possible component precipitation causing foam affecting heat exchange. Remove foam; may need defoamer; stop and circulate 24h then observe

LM-4Series Usage Precautions

LM-4 Series Usage Notes

High-temperature caution: Mild copper corrosion at 150C; use stainless steel for high-temperature applications.
System cleaning: Thoroughly clean the system before filling to remove oil and impurities. Ammonia system conversions require special attention.
Regular monitoring: Periodically test pH and inhibitor concentration; adjust promptly when abnormalities are detected.
Freezing point margin: Select freezing point 10-15C below minimum operating temperature for adequate safety margin.
Conductivity: LM-4D and LM-4D-YE conductivity must be matched to specific customer requirements; confirm needs before selection.


Post time: Aug-27-2026